                            DEPARTMENT OF THE ARMY                EP 1110-3-2

                         U.S. Army Corps of Engineers

CEMP-ET                    Washington, DC 20314-1000



Pamphlet

No. 1110-3-2                                                 31 December 1990



                            Engineering and Design

      ELECTROMAGNETIC PULSE (EMP) AND TEMPEST PROTECTION FOR FACILITIES



1. Purpose. This pamphlet provides unclassified engineering and design

information about protecting fixed ground facilities against the effects of an

electromagnetic pulse (EMP) produced by a nuclear explosion. It also provides

unclassified engineering and design information about satisfying TEMPEST

requirements.



2. Applicability. This pamphlet applies to all HQUSACE/OCE elements, major

subordinate commands, districts, laboratories, and field operating activities

(FOA) having military construction and design responsibilities.



3. Discussion. The enclosed material constitutes a general reference work on

the specialized subject of electromagnetic pulse (EMP) and TEMPEST protection.

It was assembled over several years by our Construction Engineering Research

Laboratory. The designer who is interested in the theory behind the design

will find this material useful. The designer will also find information on

aspects of the subject not normally part of the design effort.



FOR THE COMMANDER:



Encl



[Signature]

ROBERT L. HERNDON

Colonel, Corps of Engineers

Chief of Staff



------------------------------------------------------------------------------



      ELECTROMAGNETIC PULSE (EMP) AND TEMPEST PROTECTION FOR FACILITIES



                              TABLE OF CONTENTS



                                                            Paragraph  Page



CHAPTER 1.  INTRODUCTION



            Scope..............................................1-1     1-1

            Application........................................1-2     1-1

            References.........................................1-3     1-1

            Background.........................................1-4     1-2

            Pamphlet organization..............................1-5     1-2



CHAPTER 2.  EMP ENVIRONMENT



            Outline............................................2-1     2-1

            HEMP: detailed discussion..........................2-2     2-2

            Other EMP environments.............................2-3     2-5

            Environment-to-facility coupling...................2-4     2-9

            Equipment susceptibility...........................2-5     2-16

            Cited references...................................2-6     2-19

            Uncited references.................................2-7     2-20



CHAPTER 3.  EMP HARDENING CONCEPTS FOR FACILITIES



            Outline............................................3-1     3-1

            Discussion of general concepts.....................3-2     3-1

            Description of HEMP hardening concepts.............3-3     3-4

            Cited reference....................................3-4     3-10

            Uncited references.................................3-5     3-10



CHAPTER 4.  SYSTEM ENGINEERING REQUIREMENTS



            Outline............................................4-1     4-1

            Standards and specifications.......................4-2     4-1

            Electromagnetic integration........................4-3     4-2

            HEMP and lightning protection integration..........4-4     4-2

            HEMP/TEMPEST and electromagnetic integration.......4-5     4-4

            Environmental requirements.........................4-6     4-5

            Cited references...................................4-7     4-6



CHAPTER 5.  FACILITY DESIGN [not digitized here]



            Outline............................................5-1     5-1

            Theoretical approach to shielding..................5-2     5-5

            Shield design methodology..........................5-3     5-6

            Solid shields......................................5-4     5-10

            Shielded enclosures................................5-5     5-20

            Mesh and perforated type shields...................5-6     5-21

            Layered shields....................................5-7     5-27

            Reinforcement steel (rebar)........................5-8     5-27

            Earth cover electromagnetic wave attenuation.......5-9     5-30

            Shield joints and seams............................5-10    5-31

            Internal cable and connectors......................5-11    5-35

            Conduit and conduit connections....................5-12    5-38

            Terminal protection for electrical penetrations....5-13    5-43

            Apertures..........................................5-14    5-52

            Utility penetrations...............................5-15    5-55

            Bonding............................................5-16    5-55

            Grounding..........................................5-17    5-61

            Cited references...................................5-18    5-64

            Uncited references.................................5-19    5-67



CHAPTER 6.  EMP AND TEMPEST TESTING REQUIREMENTS [not digitized here]



            Outline............................................6-1     6-1

            Introduction.......................................6-2     6-3

            Testing requirements versus facility mission.......6-3     6-4

            Susceptibility testing.............................6-4     6-4

            Quality assurance testing..........................6-5     6-6

            Acceptance testing.................................6-6     6-7

            Hardness assessment and validation testing.........6-7     6-9

            Life-cycle testing.................................6-8     6-10

            Test methodology...................................6-9     6-11

            Free-field illuminators............................6-10    6-12

            Current injection testing..........................6-11    6-17

            Shielding effectiveness testing....................6-12    6-27

            Bonding impedance measurements.....................6-13    6-34

            Cited references...................................6-14    6-35

            Uncited references.................................6-15    6-36



CHAPTER 7.  PROTECTION MAINTENANCE AND SURVEILLANCE [not digitized here]



            Outline............................................7-1     7-1

            Introduction.......................................7-2     7-2

            Facility life cycle environment....................7-3     7-2

            Hardening shielding elements.......................7-4     7-3

            Impact of hardness maintenance on facility

             design............................................7-5     7-4

            Hardness maintenance program structure.............7-6     7-7

            Hardness surveillance (HS) activities..............7-7     7-10

            Cited references...................................7-8     7-13



CHAPTER 8.  EMP AND TEMPEST RISKS



            Outline............................................8-1     8-1

            Introduction.......................................8-2     8-2

            EMP environment--overview..........................8-3     8-2

            Comparison of HEMP and lightning...................8-4     8-5

            TEMPEST risks......................................8-5     8-5

            Cited references...................................8-6     8-10



CHAPTER 9.  EMP AND TEMPEST PROTECTION CONCEPTS



            Outline............................................9-1     9-1

            Introduction.......................................9-2     9-1

            TEMPEST requirement in relation to HEMP............9-3     9-4

            Generic facility hardening.........................9-4     9-5



CHAPTER 10. SYSTEMS INTEGRATION [not digitized here]



            Outline............................................10-1    10-1

            Introduction.......................................10-2    10-1

            Protection system integration......................10-3    10-2

            Internal systems...................................10-4    10-2

            Environmental systems..............................10-5    10-2

            General integration................................10-6    10-3



CHAPTER 11. DESIGN AND SPECIFICATION PROCESS [not digitized here]



            Outline............................................11-1    11-1

            Introduction.......................................11-2    11-2

            Design approach....................................11-3    11-2

            Typical design process.............................11-4    11-3

            General shield design problem areas................11-5    11-23



CHAPTER 12. TEMPEST-SHIELDED FACILITIES



            Outline............................................12-1    12-1

            Introduction.......................................12-2    12-2

            Design criteria for 50-decibel facilities..........12-3    12-2

            RF shield design for 50-decibel facilities.........12-4    12-3

            Penetration protection devices.....................12-5    12-10

            Cited references...................................12-6    12-li

            Uncited reference..................................12-7    12-11



------------------------------------------------------------------------------



                               LIST OF FIGURES



Figure  2-1.   The Compton process.....................................2-25

        2-2.   (Not used.)

        2-3.   Variations in high-altitude EMP peak electric

                field strength as a function of direction and

                distance from surface zero.............................2-27

        2-4.   HEMP waveform...........................................2-28

        2-5.   Qualitative time domain example of HEMP.................2-29

        2-6.   Qualitative frequency domain example of HEMP............2-30

        2-7.   Surface-burst EMP showing source region and

                radiated region........................................2-31

        2-8.   Overview of surface-burst EMP...........................2-32

        2-9.   Radiated vertical electric field--large

                surface burst..........................................2-33

        2-10.  Air-burst EMP--source region............................2-34

        2-11.  Air-burst EMP--radiated region..........................2-35

        2-12.  Three modes of penetration and coupling into

                shielded enclosures....................................2-36

        2-13.  Magnetic shielding effectiveness of an

                enclosure with solid walls and an

                enclosure with rebar...................................2-37

        2-14.  Magnetic shielding effectiveness of an

                ideal enclosure and an enclosure with

                openings...............................................2-38

        2-15.  Ground-based facilities--unintentional

                antennas...............................................2-39

        2-16.  EMP coupling to facility penetrations...................2-40

        2-17.  Two mechanisms by which EMP couples to

                conductors.............................................2-41

        2-18.  Equivalent circuit for a small electric

                dipole.................................................2-42

        2-19.  Equivalent circuit for a small loop (magnetic

                dipole)................................................2-43

        2-20.  Modeling example--microwave tower and

                equivalent fat cylindrical monopole....................2-44

        2-21.  Shielded cables and transfer impedance..................2-45

        2-22.  Transmission line coupling..............................2-46

        2-23.  Aerial conductors: effect of conductor length...........2-47

        2-24.  Buried conductors: effect of burial depth...............2-48

        2-25.  Ringing.................................................2-49

        2-26.  Typical internal signal cable distribution

                diagram................................................2-50

        2-27.  Intrasite cables........................................2-51

        2-28.  EMP system interaction..................................2-52

        2-29.  Energy level ranges, in joules, that damage

                various components.....................................2-53

        2-30.  Examples of transient upset.............................2-54

        2-31.  Range of pulse power damage constants for

                representative transistors.............................2-55

        2-32.  Range of pulse power damage constants for

                representative semiconductors..........................2-56

        3-1.   Building examples showing three concepts for

                critical equipment protection..........................3-11

        3-2.   Zonal shielding concept.................................3-12

        3-3.   Underground facility with four zones....................3-13

        3-4.   Zonal shielding concept with steel-reinforced

               concrete as shield 1....................................3-14

        3-5.   Shielded enclosure: cable entry vault...................3-15

        3-6.   Optical fiber shield penetration........................3-16

        4-1.   Processes and currents occurring in a flash

                to ground..............................................4-12

        4-2.   EMP and lightning comparison............................4-13

        4-3.   Sample power line surge voltage as a function

                of distance from stroke to line........................4-14

        4-4.   Typical spectrum of lightning radiated E-field..........4-15

        4-5.   Average radiated and static fields for

                lightning..............................................4-16

        5-1.   Transmission line model of shielding....................5-97

        5-2.   Correction factor in correction term for

                internal reflections...................................5-98

        5-3.   Shield absorption loss nomograph........................5-99

        5-4.   Nomograph for determining magnetic field

                reflection loss........................................5-100

        5-5.   Nomograph for determining electric field

                reflection loss........................................5-101

        5-6.   Nomograph for determining plane wave

                reflection loss........................................5-102

        5-7.   Chart for computing K for magnetic field

                secondary reflection loss..............................5-103

        5-8.   Chart for computing secondary losses for

                magnetic fields........................................5-104

        5-9.   Absorption loss for steel and copper shields at

                30 hertz to 10,000 megahertz...........................5-105

        5-10.  Absorption loss for copper and iron, in

                decibels per mil.......................................5-106

        5-11.  Shielding effectiveness in electric, magnetic,

                and plane wave fields of copper shields

                (7 mils thick) for signal sources 165 feet

                from the shield........................................5-107

        5-12.  Shielding effectiveness in electric, magnetic,

                and plane wave fields of steel shield (1 mil

                thick) for signal sources 165 feet from

                the shield.............................................5-108

        5-13.  Shielding effectiveness in electric, magnetic,

                and plane wave fields of steel shield

                (50 mils thick) for signal sources 165 feet

                from the shield........................................5-109

        5-14.  Minimum shielding effectiveness of low-carbon

                steel walls............................................5-110

        5-15.  Performance characteristics of typical commercial

                shielded enclosures....................................5-111

        5-16.  Mean shielding effectiveness for all test points

                for the June 1980 test.................................5-112

        5-17.  (not used.)

        5-18.  Aperture shielding......................................5-114

        5-19.  (Not used.)

        5-20.  (Not used.)

        5-21.  (Not used.)

        5-22.  Attenuation--rectangular waveguide......................5-119

        5-23.  Attenuation--circular waveguide.........................5-120

        5-24.  Air impedance of perforated metal and honeycomb.........5-121

        5-25.  Air impedance of copper and nickel mesh.................5-122

        5-26.  (Not used.)

        5-27.  Center area attenuation of 5-meter-high,

                single-course reinforcing steel room...................5-124

        5-28.  Center area attenuation of 10-meter-high,

                single-course reinforcing steel room...................5-125

        5-29.  Correction curves for various rebar diameters

                and spacings using single-course rebar

                construction...........................................5-126

        5-30.  Shielding degradation versus distance from wall.........5-127

        5-31.  Shielding effectiveness of reinforcement steel..........5-128

        5-32.  Reinforcement steel welding practice....................5-129

        5-33.  Schematic presentation--reinforcement steel

                shield.................................................5-130

        5-34.  Weld joints for sheet steel shields.....................5-131

        5-35.  Bolted joints for metallic shields......................5-132

        5-36.  Shielding effectiveness for bolted joints...............5-133

        5-37.  Influence of screw spacing on shielding

                effectiveness..........................................5-134

        5-38.  Gasket deflection limits (in inches)....................5-135

        5-39.  Typical mounting techniques for RF gaskets..............5-136

        5-40.  Improper gasket application.............................5-137

        5-41.  EMI shielded door seam (mesh gasket)....................5-138

        5-42.  EMI shielded door seam ("oval" spiral gasket)...........5-139

        5-43.  EMI shielded door seam (fingerstock)....................5-140

        5-44.  Shielding effectiveness and transfer impedance..........5-141

        5-45.  A braided-shield coaxial cable..........................5-142

        5-46.  Cable shielding effectiveness with number

                of braid layers........................................5-143

        5-47.  Lossy conductor construction............................5-144

        5-48.  Attenuation of HEMP interference propagating

                on lossy-wrapped conductors............................5-145

        5-49.  Induction loop area for twisted pair cables.............5-146

        5-50.  Experiments with shielded twisted pair cabling..........5-147

        5-51.  Construction of some popular coaxial connectors.........5-148

        5-52.  Contact resistance of conductive coatings

                on aluminum............................................5-149

        5-53.  Shielding effectiveness of connectors with

                various finishes.......................................5-150

        5-54.  Effect of tightening torque on shielding

                effectiveness during vibration.........................5-151

        5-55.  Effect of added spring fingers on shielding

                effectiveness..........................................5-152

        5-56.  Effect of adding shielding gaskets on connector

                shielding effectiveness................................5-153

        5-57.  Normalized transfer impedance for solid

                cylindrical shields....................................5-154

        5-58.  Magnitude of the transfer impedance of rigid

                steel conduit..........................................5-155

        5-59.  Flaw impedance (ZF) of typical coupling.................5-156

        5-60.  Diffusion signal for 1-inch galvanized steel

                conduit showing sense wire voltage.....................5-157

        5-61.  Flaw impedance (ZF) of 0.038-millimeter

                (0.015-inch) wall flex-joint with and without

                copper strap...........................................5-158

        5-62.  Flaw impedance (ZF) of 0.76-millimeter

                (0.03-inch) wall flex-joint with and without

                 copper strap..........................................5-159

        5-63.  Experimental HEMP hardened union........................5-160

        5-64.  Type C conduit body.....................................5-161

        5-65.  Machined conduit body cover for HEMP hardening..........5-162

        5-66.  "Wrap-around" junction box cover........................5-163

        5-67.  (Not used.)

        5-68.  (Not used.)

        5-69.  (Not used.)

        5-70.  (Not used.)

        5-71.  The four basic filter classes...........................5-168

        5-72.  Ferrite bead on wire and ferrite bead equiv-

                alent circuit..........................................5-169

        5-73.  Filter pin connector design.............................5-170

        5-74.  Shunt and series transformer wiring

                configuration..........................................5-171

        5-75.  Typical shielded door closures..........................5-172

        5-76.  Emergency escape hatch configuration....................5-174

        5-77.  Typical welded screen installation over a

                ventilation aperture...................................5-175

        5-78.  Typical clamped screen installation over a

                ventilation aperture...................................5-176

        5-79.  Honeycomb material for shielding air vents..............5-177

        5-80.  Waveguide attenuation as a function of

                waveguide dimensions...................................5-178

        5-81.  Air vent HEMP protection design.........................5-179

        5-82.  Conduit or metal pipe penetration design................5-180

        5-83.  HEMP protection for waveguide entry.....................5-181

        5-84.  Plastic pipe termination practices......................5-182

        5-85.  Theoretical attenuation of the TE11 mode

                for a 1.5-inch (3.8-centimeter) internal

                diameter pipe with distilled water for

                various loss tangents..................................5-184

        5-86.  Cutoff frequency versus relative dielectric

                constant for various pipe diameters....................5-185

        5-87.  Effects of poor bonding on the performance

                of a power line filter.................................5-186

        5-88.  Bolted bond between flat bars...........................5-187

        5-89.  Bracket installation (bolt).............................5-188

        5-90.  Bonding of connector to mounting surface................5-189

        5-91.  Bolting of bonding jumpers to flat surface..............5-190

        5-92.  Bonding to rigid conduit................................5-191

        5-93.  Equivalent circuit for bonding strap....................5-192

        5-94.  True equivalent circuit of a bonded system..............5-193

        5-95.  Techniques for protecting bonds between

                dissimilar metals......................................5-194

        5-96.  Zonal grounding.........................................5-195

        5-97.  Minimum earth electrode system configuration

                for rectangular--shaped facility.......................5-196

        5-98.  Electrode configuration for irregular-shaped

                facility...............................................5-197

        5-99.  Current path on zonal boundaries........................5-198

        5-100. Typical hybrid ground configuration.....................5-199

        5-101. Typical ground configurations for HEMP

                protection.............................................5-200

        6-1.   Bounded wave simulators.................................6-43

        6-2.   Pulsed radiated wave simulators.........................6-44

        6-3.   Continuous wave testing--CW test configuration..........6-46

        6-4.   Direct current injection testing........................6-47

        6-5.   Inductive current injection testing.....................6-48

        6-6.   Direct drive test for penetrating conductor

                (conceptual sketch)....................................6-49

        6-7.   Transfer impedance/admittance test setup................6-50

        6-8.   Alternative demonstration and test methods..............6-51

        6-9.   Response characteristic measurement.....................6-52

        6-10.  Standard circuit for measuring S parameters.............6-53

        6-11.  Response measurement....................................6-54

        6-12.  HEMP stress test........................................6-55

        6-13.  TPD power attenuation test..............................6-56

        6-14.  Alternative power attenuation test using

                simulated subsystem impedance..........................6-57

        6-15.  Static breakdown voltage measurement....................6-58

        6-16.  Small-loop-to-small-loop test setup.....................6-59

        6-17.  Proposed measurement points for small-loop

                test...................................................6-60

        6-18.  Test setup for Helmholtz coil field

                generation.............................................6-61

        6-19.  Parallel strip line technique...........................6-62

        6-20.  Attenuation measurement--high-impedance

                electric field.........................................6-63

        6-21.  Attenuation test for plane waves (wave

                impedance = 377 ohms)..................................6-64

        6-22.  Parallel plate line.....................................6-65

        6-23.  Sweep frequency bonding measurement system..............6-66

        7 1.   Effect of hardening approach on subsystem

                design.................................................7-15

        7-2.   Interaction of HM/HS/TSM program elements...............7-16

        7-3.   Configuration management process........................7-17

        7-4.   Example of maintenance procedures.......................7-18

        8-1.   Near-surface and exoatmospheric blasts..................8-13

        8-2.   Time waveform for the free-field HEMP

                electric field.........................................8-14

        8-3.   HEMP ground coverage for bursts of various

                heights above the United States........................8-15

        8-4.   Reasonable worst-case TEMPEST shielding

                attenuation requirement................................8-16

        8-5.   Fifty-decibel (nominal) TEMPEST pipe or air

                duct penetration design................................8-17

        11-1.  Required electromagnetic attenuation....................11-32

        11-2.  Checklist for HEMP drawings.............................11-33

        12-1.  Efficient TEMPEST facility floor plan...................12-12

        12-2.  Typical clamped modular shield room joints..............12-13

        12-3.  Typical penetration panel installation in a

                modular shielded enclosure.............................12-14

        12-4.  Steel plate floor shield design.........................12-15

        12-5.  Floor plate shield construction technique...............12-16

        12-6.  Foil wall shield construction technique.................12-17

        12-7.  Foil/foil seam..........................................12-18

        12-8.  Sheet metal/foil seam...................................12-19

        12-9.  Foil shield pipe penetration design.....................12-20



------------------------------------------------------------------------------



                                LIST OF TABLES



Table 2-1.   Important features of EMP environments....................2-21

      2-2.   EMP waveform summary......................................2-22

      2-3.   Response thresholds.......................................2-23

      2-4.   Typical EMP transients and equipment

              thresholds--EMP threat level.............................2-24

      4-1.   HEMP/TEMPEST-related standards and

              specifications...........................................4-8

      4-2.   Peak magnetic field values for close lightning

              strokes..................................................4-11

      5-1.   Coefficients for magnetic field reflection loss...........5-69

      5-2.   Absorption loss of metals at 150 kilohertz................5-70

      5-3.   Absorption loss of solid copper, aluminum, and

              iron shields at 60 hertz to 10,000 megahertz.............5-71

      5-4.   Reflection loss...........................................5-72

      5-5.   Shield effectiveness in magnetic field (wave

              impedance much smaller than 377 ohms) of solid

              copper, aluminum, and iron shields for signal

              source 12 inches from the shield at 150 kilo-

              hertz to 100 megahertz...................................5-73

      5-6.   Shielding effectiveness in plane wave field

              (wave impedance equal to 377 ohms) of solid

              copper and iron shields for signal sources

              greater than 2 inches from the shield at 150

              kilohertz to 100 megahertz...............................5-74

      5-7.   Shielding effectiveness in electric field (wave

              impedance much greater than 377 ohms) of solid

              copper, aluminum, and iron shields for signal

              source 12 inches from the shield at 0.15

              megahertz to 100 megahertz...............................5-75

      5-8.   Re-reflection (B) factors in electric, magnetic,

              and plane wave fields of solid copper and iron

              shields..................................................5-76

      5-9.   Shielding effectiveness in electric, magnetic,

              and plane wave fields of copper shield (7 mils

              thick) for signal source 165 feet from the

              shield at 30 hertz to 10 gigahertz.......................5-78

      5-10.  Shielding effectiveness in electric, magnetic,

              and plane wave fields of steel shield (1 mil

              thick) for signal source 165 feet from the

              shield at 30 hertz to 10 gigahertz.......................5-79

      5-11.  Shielding effectiveness in electric, magnetic,

              and plane wave fields of steel shield (50 mils

              thick) for signal source 165 feet from the shield

              at 30 hertz to 10 gigahertz..............................5-80

      5-12.  Sample calculations of shielding effectiveness

              for solid metal shield...................................5-81

      5-13.  Peak voltage induced on 10-meter radius loop

              inside 10-meter radius spherical shield by the

              high-altitude EMP (by diffusion through the

              walls only)..............................................5-83

      5-14.  Effectiveness of nonsolid shielding materials

              against low-impedance and plane waves....................5-84

      5-15.  Effectiveness of nonsolid shielding materials

              against high-impedance waves.............................5-85

      5-16.  Comparison of measured and calculated values of

              shielding effectiveness for No. 22, 15-mil

              copper screens...........................................5-86

      5-17.  (Not used.)

      5-18.  Application factors for welded wire fabric................5-88

      5-19.  Typical values of conductivity for soils

              and rock.................................................5-89

      5-20.  Skin depth (d) and absorption loss (A) for

              nonmetal materials.......................................5-90

      5-21.  Electromotive series......................................5-91

      5-22.  Characteristics of conductive gasketing

              materials................................................5-92

      5-23.  (Not used.)

      5-24.  Comparison of protection devices..........................5-94

      5-25.  Galvanic series for selected metals.......................5-95

      5-26.  Relative advantages and disadvantages of the

              principal types of earth electrodes......................5-96

      6-1.   Test applicability........................................6-37

      6-2.   Summary of existing bounded-wave simulators...............6-38

      6-3.   Summary of radiating wave simulators......................6-39

      6-4.   Scaling relationships.....................................6-40

      6-5.   Summary of quality assurance test methods.................6-41

      6-6.   Comparison of shielding effectiveness test

              methods..................................................6-42

      7-1.   Qualitative tradeoff study results........................7-14

      8-1.   Comparison of HEMP with lightning-induced

              stresses on long overhead power lines....................8-12

      11-1.  Power line surge arrester criteria........................11-26

      11-2.  Power line filter criteria................................11-27

      11-3.  Signal and control line protection: coaxial

              penetrations.............................................11-28

      11-4.  Twisted shielded pair criteria............................11-29

      11-5.  Terminal protection device................................11-30

      11-6.  Shielding effectiveness test points.......................11-31



------------------------------------------------------------------------------





                                   CHAPTER 1 



                                 INTRODUCTION



1-1. Scope.



   a. Focus. The focus in this pamphlet is on electromagnetic pulse (EMP) 

produced by nuclear explosions at high altitudes (high-altitude EMP, or HEMP). 

Herein, the terms EMP and HEMP are used synonymously. In many cases 

facilities are not targeted for other nuclear effects and a HEMP event is the 

worst-case scenario for ground-based facilities. Therefore, many protective 

measures described herein will also protect against some other electromagnetic 

environments.



   b. Subjects not covered. Specific protection methods for other types of 

EMP, such as source-region EMP and surface-burst EMP are not covered. In 

addition, this pamphlet does not cover protection against other effects of 

nuclear explosions (for example, blast overpressure and thermal/nuclear 

radiation).



   c. TEMPEST problem. The TEMPEST problem is nearly the inverse of the HEMP 

event. TEMPEST is the unclassified name for the studies and investigation of 

compromising emanations. Equipment within the facility can be the source of 

electromagnetic waves and stray currents/voltages with characteristics which 

are related to the information content of signals being processed. If these 

unintentional emissions are intercepted and studied, the analyst can 

reconstruct the original data and could gain access to national security 

information A proper TEMPEST design, however, will preclude the presence of 

analyzable signals in uncontrolled areas.



   d. Common treatment. Thus, HEMP and TEMPEST protective measures must each 

control electromagnetic energy, the former protecting system equipment from 

externally generated signals and the latter containing emissions from internal 

sources. The functional similarities imply that a common treatment can be 

employed for the two purposes.



1-2. Application. Information in this pamphlet is applicable to engineers 

responsible for the design, construction, and maintenance of mission-critical 

facilities, such as those supporting the command, control, communications and 

intelligence network. The information is relevant to new construction as well 

as to additions, upgrades, and retrofits to existing facilities.



1-3. References. This pamphlet is intended to stand alone and, as such, no 

additional references should be required to understand the material herein. 

However, only a small sample of the material published on HEMP and TEMPEST can 

be highlighted here. Because different facilities will have differing 

requirements for protection, supplementary sources are listed at the end of

most chapters to assist the engineer in designing protection on a case-by-

case basis.



1-4. Background.



   a. Reliance on electronic technology. Military facilities are becoming 

increasingly reliant on automated systems that take advantage of modern 

electrical and electronic technology. Facilities are equipped with state-of

the-art computerized systems for expeditious, reliable, and cost-effective 

operations. However, the electromagnetic (EM) properties of many electronic 

components can make entire systems susceptible to upset or permanent damage 

due to the environmental effects of EMP. Systems are also susceptible to the 

compromise of security information by the unintentional intelligence-bearing 

emanations of electromagnetic signals. Thus, with the benefits of automation 

has come an increased vulnerability.



   b. Early planning. Techniques to protect a facility are usually selected 

during the early design phase. If it is anticipated that a facility may 

someday acquire equipment that must be protected, early planning can avoid 

costly retrofitting later. The decision to harden will be based on the 

interaction of mission criticality, electromagnetic environment, security 

requirements, and costs.



   c. Far-reaching effects. HEMP is dangerous because this event has far-

reaching effects at distances where other nuclear environments are either 

nonexistent or inconsequential and because of its high level of broad spectral 

energy. However, the spectrum included under HEMP does not cover all EM 

environments. For example, the characteristic pulse risetime and possible 

conducted current waveforms for lightning differ from those for HEMP; thus, 

hardening against HEMP does not necessarily protect against lightning.



   d. Evolving technology. It is important to note that this field is 

relatively new and that technical expertise is still evolving. Therefore, it 

is the designer's responsibility to stay current with new developments to 

assure the most cost-effective reliable configuration for vital military fixed 

facilities.



1-5. Pamphlet organization. At the beginning of each subsequent chapter, 

there is an outline. The purpose of the outline is to provide more detail on 

the chapter's content than is ordinarily appropriate in a table of contents.



------------------------------------------------------------------------------

[End Chapter 1]